The monitoring unit RLAnet is a component of the BARTEC Water leakage detection system. It is operating with the sensor cable SCR and/or the point sensor PS. The system detects minor liquid leakages fast and reliable.
The monitoring unit RLAnet is a component of the BARTEC Water leakage detection system. It is operating with the sensor cable SCR and/or the point sensor PS. Further components of the BARTEC Water leakage detection system are the monitoring units RLW, RDW 03 and RDA 01, also the accessories. The system detects minor liquid leakages fast and reliable. An optical and acoustic signal arises. Simultaneously the potential-free contact switches. This can be used for signalling to PLC or to a building control unit. The leakage is being localized exact by 1 meter and get visualized on the 4-digit display. Thus a leakage will be found by a service person quick and true.
Visualization The service-software (for WINDOWS-PC) calls the system status via RS485 in real-time. The data is available in MODBUS RTU protocol. Up to 250 MODBUS addresses will be handled. The typical application parametrization will also be managed by using this service-software.
Download the service software and the extended manual below: www.bartec.de
Application Areas:
| TECHNICAL DATA | |
| Power supply | DC 12 V to 24 V ±10 %; 3 W |
| Method of measurement | conductive (conductive liquids > 30 µS/cm) accuracy: ±1 % |
| Inputs | Sensor via 4-wire cable Sensor cable length: max. 500 m Point sensors: max. 50 pieces Sensitivity: adjustable |
| Outputs | Collective message alarm relay, 1 floating change-over contact AC 12: 0.5 A, 125 V DC 13: 1 A, 24 V RS485, Modbus RTU, for process visualization and parametrization |
| Memory | Alarm-/Break storage, last 32 happenings |
| Signal optical | Power LED red, relay de-energized Leak LED green, relay energized Service LED green, relay energized |
| Signal acoustic | Piezoelectric buzzer quit by pressing button on front panel |
| Ambient temperature | -20 °C to +50 °C at 5 % to 95 % air humidity (non-condensing) |
| Storage temperature | -40 °C to +60 °C |
| Protection class | IP 20 |
| Housing material | Thermoplastic |
| Mounting | Clip-on enclosure for mounting rail TS 35 |
| Dimensions (W x H x D) | 70 mm x 86 mm x 53 mm |
| SCR sensor cable |
Terminal 13, white, perforated Terminal 14, white, insulated Terminal 15, red, perforated Terminal 16, red, insulated |
| Point sensor PS terminal via installation cable |
Terminal 13, 1 (e.g. white LIYY) Terminal 14, 2 (e.g. brown LIYY) Terminal 15, 3 (e.g. green LIYY) Terminal 16, 4 (e.g. yellow LIYY) |
The monitoring unit RLAnet is a component of the BARTEC Water leakage detection system. It is operating with the sensor cable SCR and/or the point sensor PS. Further components of the BARTEC Water leakage detection system are the monitoring units RLW, RDW 03 and RDA 01, also the accessories. The system detects minor liquid leakages fast and reliable. An optical and acoustic signal arises. Simultaneously the potential-free contact switches. This can be used for signalling to PLC or to a building control unit. The leakage is being localized exact by 1 meter and get visualized on the 4-digit display. Thus a leakage will be found by a service person quick and true.
Visualization The service-software (for WINDOWS-PC) calls the system status via RS485 in real-time. The data is available in MODBUS RTU protocol. Up to 250 MODBUS addresses will be handled. The typical application parametrization will also be managed by using this service-software.
Download the service software and the extended manual below: www.bartec.de
Application Areas: