It is used in the fields of freeze prevention, temperature maintenance, pipelines, chemical and petrochemical, marine and offshore, food processing, industrial water and sanitation facilities.
The self-regulating heating cable, certified with ATEX and safely operable at 65°C/80°C, is also an ideal solution for structural and light industrial areas.
Applications:
Advantages:
Design:
Approvals:
| 1) Bus wire | Nickel plated copper |
| 2)Self-regulating heating element | PTC – Positive Temperature Coefficient technology |
| 3)Insulation | Fluoropolymer |
| 4) Protection | Protective braid (Cu, tin plated) |
| 5) Outer jacket | TPE-O |
| 6) Protective conductor connection | See 4 or Cu, tin plated with aluminium foil |
| TECHNICAL INFORMATION | |
|---|---|
| Maximum ambient temperature, energized | 65 °C |
| Maximum ambient temperature, de-energized | 80 °C |
| Nominal voltage* | 230 V |
| Bending radius, min. | 25 mm |
| Installation temperature, min. | – 60 °C |
| Type | Nominal Output | Dimensions approx. (mm) | Weight approx. (g/m) | Part No. |
|---|---|---|---|---|
| ELSR-LS-10-2-BO | 10 W/m at 10 °C | 11.0 x 5.6 | 98 | B0223102 |
| ELSR-LS-10-2-AO | 10 W/m at 10 °C | 10.3 x 5.3 | 78 | B0223104 |
| ELSR-LS-15-2-BO | 15 W/m at 10 °C | 11.0 x 5.6 | 98 | B0223152 |
| ELSR-LS-15-2-AO | 15 W/m at 10 °C | 10.3 x 5.3 | 78 | B0223154 |
| ELSR-LS-25-2-BO | 25 W/m at 10 °C | 11.0 x 5.6 | 98 | B0223252 |
| ELSR-LS-25-2-AO | 25 W/m at 10 °C | 10.3 x 5.3 | 78 | B0223254 |
The self-regulating heating cable, certified with ATEX and safely operable at 65°C/80°C, is also an ideal solution for structural and light industrial areas.